Welcome to Online Power, Inc - protector

By: Online Power  09-12-2011
Keywords: Battery, Cabinet Sizes, External Battery,


Protector




Specifications

  Power Rating 3, 5, 7.5, 10, 12.5, 15, & 20 KVA
  Input Voltage 120 (3 & 5 KVA only), 208, 240,or 277 VAC, +15% to -20%
  Output Voltages 120, 208, 240, 120/240, and 277 VAC (All Standard with output transformer)
  Output Frequency
(Inverter Operation)
60 Hz ±0.5 Hz
  OutputVoltage
Regulation
±3%
  Output Wave Form Sine-Wave < 5% THD.
  Efficiency 90%
  Crest Factor 3:1 Typical
  Surge Protection The UPS will protect itself and the
load against surges as defined in
ANSI/IEEE C62.41 Categories A
and B.
  Isolation Complete from line. Output neu-tral
bonded to ground (with otuput
transformer only)
  Noise Isolation -120 dB Common-Mode;
-60 dB Transverse-Mode
  Battery Sealed maintenance-free (AGM) battery
  Battery Voltage KVA dependent
  Recharge Time Conforms to UL Standards
  External Battery Provisions for hardwire connec-tion
of optional external battery cabinets or DC source.
  Environmental
  Humidity
0 - 95% RH w/ no condensation
     Operating Temp. UPS: 0° to 40°C. (32° - 104°F)
Battery: 20° to 30°C. (68° - 86°F)
     Storage Temp. -20° to 60°C. (-4° - 140°F)
     Altitude Up to 10,000 ft
  Safety Agencies CUL, CSA Listed to UL1778,
MEA Approved; State Fire
Marshal Approved (CA, NY, IL)
  Cabinet Sizes with
Standard Run Times
(W x H x D)
18" x 35" x 32"
29" x 68" x 18"
  Other Cabinet Sizes dependent on Battery Run Time
       Copyright © 2002 Onlinepower, Inc. All rights reserved.

Keywords: Battery, Battery Cabinets, Cabinet Sizes, External Battery,

Other products and services from Online Power

09-12-2011

Welcome to Online Power, Inc - tbs

LU 750: 300 lbs. LU 1500: 450 lbs. 120 VAC or 208 VAC.


09-12-2011

Welcome to Online Power, Inc - harsh env

Suitable for Harsh Environment, Outdoor Applications AC Line Conditioning for Signals, Signs & Lighting Small Foot Print Meets NEMA Requirements Fail-Safe Provision Optional Global Monitoring System 2 year Factory Warranty. Provisions for hardwire connec-tionof optional external battery cabinets or DC source. Specifications are subject to change without prior notification. 120 (3 & 5 KVA only), 208, 240,or 277 VAC, +15% to -20.


09-12-2011

Welcome to Online Power, Inc - singlewave

Provisions for hardwire connection of optional external battery cabinets or DC source. Cabinet Sizes (with Standard Battery Run Times) All model. 5 KVA/KW;120, 208, 240, 277, or 480 VAC. 15 KVA/KW; 208, 240, 277, or 480 VAC.