Output and Power Consumption

Model Power Capacity Amperage # of
outlets
Dia. of
Outlets
240/1 208/1 208/3 480/1 480/3 600/1 600/3
SK302 2 Kw 6 lb/hr
2.73 kg/hr
8.5 10 - 4.5 - 3.5 - 1 1-3/8"
SK304 4 Kw  12 lb/hr
5.5 kg/hr
17 19 - 8.5 - 7 - 1 1-3/8"
SK306 6 Kw  18 lb/hr
8 kg/hr
26 30 - 13 - 10.5 - 1 1-3/8"
SK309 9 Kw  27 lb/hr
12 kg/hr
-   25 - 11 - 9 1 1-3/8"
SK311 11 Kw  33 lb/hr
14.5 kg/hr
-   31 - 13.2 - 10.5 1 1-3/8"
SK314 13.5 Kw  40 lb/hr
19 kg/hr
-   38 - 16.5 - 13.5 1 1-3/8"
SK320 20 Kw  60 lb/hr
28 kg/hr
-   57 - 25 - 20 1 1-3/8"
SK330 30 Kw  90 lb/hr
41 kg/hr
-   - - 36 - 30 2 1-3/8"
SK340 40 Kw  120 lb/hr
56 kg/hr
-   - - 50 - 40 2 2-1/8"
SK360 60Kw  180 lb/hr
82 kg/hr
-   - - 72 - 60 3 2-1/8"

Note: designate the letter M for modulating units. (ie: SK320M)

designate the letter D for units operating with deionized water.

* check with factory for availability.


Contact Northern Industrial Fans

Email

Print this page

Other products and services from Northern Industrial Fans

09-12-2011

Nisco - humidifiers

The AFEC system is made of a mass measuring water sensor, anti-foam sensor, electronic high temperature sensor, interactive LCD display and microprocessor controller. The AFEC technology developed by the N.E.P. engineering team offers a unique safety and energy conservation management of expensive boiling water and steam. The drain can be initiated only when necessary without having continuous skimming to drain expensive boiling water.


09-12-2011

Nisco - air handling units

Possible configurations include the addition of either a v-bank or an evaporative cooler intake module and a direct fired or indirect fired heating module. All modules bolt together to form a rigid common base structure that mount onto a single curb structure or can be hung for indoor applications. The blower module has a standard horizontal inlet designed to accommodate an outside air inlet hood with a standard 2" filters and screen.


09-12-2011

Nisco - heat exchangers

We can design and manufacture coils that are ideal for a wide variety of basic, custom and heavy-duty industrial applications to cool air or gas for comfort, dehumidification, dry cooling, solvent removal and other cooling applications. In addition, we can also produce coils that are perfect for accommodating the rigors of higher temperature applications such as preheating, drying, heat treatment, heat recovery and/or removal.


09-12-2011

Nisco - ventilators

With many commercial and industrial buildings such as factories, warehouses, parking garages, shopping malls and department stores a means of venting hot gases and smoke in the event of a fire is required. Type J PRVs are suggested for use in commercial and industrial applications including factories, warehouses, commercial buildings, machine rooms or any situation requiring the movement of air.